SA2100 Power Quality Analyzer is the professional potable device to measure and analyze the power system quality, supply the harmonics analysis and power quality data analysis, also provide big memory for the data storage, which is used to make the long term logger measuring to power system.
Input | |||
Voltage Input | |||
Input channels | 4 (3 phase + neutral) DC coupling | ||
Max. Input Voltage | 1000Vrms | ||
Range of nominal voltage | 50 ~ 500V | ||
Max pulse peak voltage | 6kV | ||
Bandwidth | 3kHz | ||
Input impedance | 4MΩ/5pF | ||
Current Input | |||
Numbers of input | 4 (3 phase + neutral) DC coupling | ||
Type | Clamp Current Sensor, with mV output | ||
Input range | 1 to 3000Arms with supplied current clamp | ||
Input impedance | 50kΩ | ||
Bandwidth | 3kHz | ||
Sampling System | |||
Resolution | 8 channels 16 bits AD | ||
Sampling rate | 20kS/s for each channel, 8 channels sample synchronously | ||
RMS sampling | 5000 points for 10/12 cycles (according to IEC 61000-4-30) | ||
PLL sync. | 4096 points for 10/12 cycles (according to IEC61000-4-7) | ||
Measurement | Measurement range | Resolution | Accuracy |
Voltage/Current/Frequency | |||
Vrms(AC+DC) | 1~1000Vrms | 0.1Vrms | ±0.5% of nominal voltage |
Vpk | 1~1400Vpk | 0.1Vpk | ±0.5% of nominal voltage |
V(Crest Factor) | 1.0~2.8 | 0.01 | ±5% |
Arms (supplied current clamp) | 1~1000A/3000/5000A | 1A | ±1%±2A |
1~100A | 0.1A | ±1%±0.2A | |
Apk | 1~4000Apk | 1A | ±1%±2A |
A(Crest Factor) | 1~10 | 0.01 | ±5% |
Frequency | 42.5~57.5 (50Hz nominal) | 0.01Hz | ±0.01%Hz |
51~69 (60Hz nominal) | 0.01Hz | ±0.01%Hz | |
Dips&Swells | |||
Vrms1/2 | 0~200% nominal voltage | 0.1Vrms | ±1% |
Arms1/2 | 1~3000A | 1A | ±1%±2A |
Threshold value | Threshold is settable according to nominal voltage percentage Detectable events type: Dips, Swells, Interruption, Voltage Rapid Change. | ||
Duration | hour-minute-second-microsecond | 0.5 period | 1 period |
Harmonic | |||
Harmonic number | 1~50 | ||
Inter-harmonic | 1~49 | ||
Harmonic voltage | 0.0~100.0% | 0.10% | ±0.1%±n×0.1% |
Harmonic current | 0.0~100.0% | 0.10% | ±0.1%±n×0.1% |
THD | 0.0~100.0% | 0.10% | ±2.5% |
DC relative | 0.0~100.0% | 0.10% | ±0.2% |
Frequency | 0~3500Hz | 1Hz | 1Hz |
Phase | -360°~ 0° | 1° | ±n×1.5° |
Power and Energy | |||
Active power/apparent Power/reactive power | 1.0~20.00MW | 0.1kW | ±1.5±10 digits |
Energy | 0.00kWh~200GWh | 10Wh | ±1.5±10 digits |
Power Factor | 0~1 | 0.01 | ±0.03 |
Flicker (only for SA2100) | |||
Pst (1min), Pst, Plt, PFS | 0.00~20.00 | 0.01 | ±5% |
Unbalance | |||
Voltage | 0.0~5.0% | 0.10% | ±0.5% |
Current | 0.0~20.0% | 0.10% | ±1% |
Voltage Phase | -360°~ 0° | 1° | ±2 digits |
Current Phase | -360°~ 0° | 1° | ±5 digits |
Voltage Transient | |||
Vpk | ±6000Vpk | 1V | ±15% |
Vrms | 10~1000Vrms | 1V | ±2.5% |
Min test time | 50μs | ||
Sampling rate | 20kS/s | ||
Inrush current | |||
Arms (AC+DC) | 0~3000Arms | 0.1 | ±1%±5 digits |
Inrush Duration | 6s~32min selectable | 10ms | ±20ms |
Logger | |||
Recording | user-defined parameters for 4 phases at the same time | ||
Memory | Data stored in TF card, 8GB | ||
Duration Time | 2 hrs to 1 year | ||
Interval | 1s to 1 hrs | ||
Wiring Combinations | |||
1Ø+NEUTRAL | Single phase with neutral | ||
1Ø SPLIT PHASE | Split phase | ||
1Ø IT NO NEUTRAL | Single phase system with two phase voltages without neutral | ||
3Ø WYE | 3-phase 4-wire system, Y type | ||
3Ø DELTA | 3-phase 3-wire system delta (Delta) | ||
3Ø IT | 3-phase Y type without neutral | ||
3Ø HIGH LEG | 4-wire 3-phase delta system (Delta) with center tapped high leg | ||
3Ø OPEN LEG | Open-delta (Delta) 3-wire system with two transformer windings | ||
2-ELEMENT | 3-phase 3-wire system without current sensor on phase L2/B (2 Watt meter method) | ||
2 1/2-ELEMENT | 3-phase 4-wire system without voltage sensor on phase L2/B | ||
General Characteristics | |||
Display | 5.6 inch 320× 240 Color TFT LCD | ||
Brightness | Adjustable | ||
Interface | USB Host,LAN | ||
Memory | 128M Flash memory ;Standard 8G TF card | ||
Dimension | 262mm*173mm*66mm | ||
Weight | 1.6 kg | ||
Battery | Rechargeable Ni-Mh 7.2V 3.8Ah,7 hours working time,4 hours charging time | ||
Standard | |||
Measurement method | IEC61000-4-30 Class-S | ||
Measurement performance | IEC61000-4-30 Class-S | ||
Power quality monitoring | EN50160 | ||
Flicker | IEC61000-4-15 | ||
Harmonic | IEC61000-4-7 | ||
Electrical Safety | |||
Comply with | IEC61010-1, Safety Degree:600V CAT IV 1000V CAT III | ||
Max.Voltage at voltage input | 600V CAT IV 1000V CAT III | ||
Max.Voltage at current input | 42Vpk |
Model | SA2100 | SA2200 |
Standard compliance | IEC61000-4-30 Class S | IEC61000-4-30 Class A |
Volt Amp Hz | ● | ● |
Dips and swell | ● | ● |
Harmonics | ● 50th Max. | ● 100th Max. |
Power and energy | ● | ● |
Unbalance | ● | ● |
Monitor | ● | ● |
Inrush | ● | ● |
Flicker | ● | ● |
Transients | ● | ● |
400Hz | ● | ● |
Wave Recording | x | ● |
Sample rate | 20kS/s | 163.84kS/s (50/60Hz) |
TF Card | 8GB | 32GB |
Battery | NI-MH, 7.2V 3.8Ah | Lithium ion,7.4V 5200mAh |
GPS/Beidou time synchronization | x | ● (option) |
WIFI | x | ● |
Input Impedance | 50kΩ | 100kΩ |
Dimension | 262mm×173mm×66 mm | 270mm×190mm×66mm |
Weight | 1.6kg | 2.0kg |
*From: |
Enter your email |
*Message: |
Enter your Message |